Solar Photovoltaic Hardening for Resilience – Wildfire

This content explores the regions in the United States facing the highest wildfire risks and provides an overview of the diverse strategies available to photovoltaic (PV) system professionals, including designers, installers, owners, and operators, to effectively manage this risk. 

These strategies encompass the entire PV system lifecycle, ranging from initial design considerations to post-damage assessments. In instances where existing approaches may be insufficient, this content raises critical research questions to further explore and enhance wildfire mitigation measures.

On This Page:

Map illustrating the solar irradiance across the United States.
Figure 1. Total Solar Resource Availability in the United States
National Laboratory of the Rockies

The National Laboratory of the Rockies' National Solar Radiation Database shows that solar PV systems are best able to reliably take advantage of the sun's energy in the Southwestern United States. Figure 1 shows the areas with highest solar resource in the United States.

These same areas are also among the most wildfire-prone areas in the country. The threat of wildfire can pose long-term survivability challenges for solar PV systems in these areas and limit power production. 

Risk Profile

 Generally, most locations in the United States have some degree of wildfire hazard potential. Figure 2 shows the areas of the United States by their wildfire hazard potential, from "Very Low" to "Very High". 

The highest fire risk in the United States occurs in the West, mainly in the mountainous and forested areas occurring west of the Rocky Mountains (i.e., in Arizona, California, Colorado, Idaho, Montana, Nevada, New Mexico, Oregon, Utah, Wyoming, and Washington).

The exceptions to this pattern are mostly large wetlands in the southern and southeastern United States or unique ecosystems with high fuel volumes near large bodies of water (i.e., dispersed areas throughout the Hawaiian Islands and the Alaskan Interior, the Gulf Coast-facing border of Texas and Louisiana, the Everglades in southern Florida, the Outer Banks of North Carolina, central New Jersey, and northern Minnesota).

The southern and southeastern United States generally have the next highest risk levels of wildfire hazard potential after the western region. Significant sections of Alabama, Florida, Georgia, Mississippi, and the Carolinas report having a "Moderate" or "High" risk of wildfire hazard.

A map illustrating wildfire hazard potential across the United States.
Figure 2 Wildfire Hazard Potential in the United States
U.S. Forest Service

Given that nearly nine in 10 wildfires are caused or started by humans rather than natural phenomena, any area with dry vegetation has some degree of risk of catching fire but the areas with "Very High" risk are those with enough fuel to keep wildfires burning and expanding.

Climate change is expected to escalate the scope and intensity of wildfire events in the United States. By 2050, wildfires may expand both in terms of the area they consume and the duration they persist, leading to heightened levels of airborne pollution and an increased frequency of occurrence.

These data suggest that solar PV systems will be more vulnerable to being affected or destroyed by wildfires. Figure 3 shows the relative increase in wildfire probability by county in the United States. This map shows that most severe increases in wildfire probability will occur in parts of California, Nevada, North Dakota, Montana, Oregon, and Texas.

A map illustrating the likelihood of wildfire risk in the next 30 years.
Figure 3 Increase in Wildfire Probability by U.S. County, 2050
First Street Foundation

Risks to Solar Photovoltaic Systems

Two primary risks are associated with wildfire hazards for PV systems. The first involves the buildup of ash and particulate matter in the atmosphere and on PV modules, which can disrupt the power generation of these systems. The second risk pertains to the potential destruction of PV systems themselves if a wildfire spreads rapidly and engulfs them.

Loss in Production

Smoke produced by wildfires can travel hundreds of miles or more from the site of a wildfire and impact the air quality and sunlight available in an area. As a result, wildfires can affect PV systems that are a great distance away from the site of burning through reduced power output and lost revenue. 

Among the PV Reliability Operations and Maintenance (PVROM) dataset sites in the western United States (i.e., Arizona, California, Idaho, Nevada, New Mexico, Utah), wildfire smoke caused a measured drop from 9.4% to 37.8% in power production.

Other research covering wildfires in California in September 2020 shows that power output by PV declined between 10% to 30% on the statewide scale but declined up to 58% locally. 

Even if wildfires leave PV systems physically undamaged, they can cause their operators to lose significant amounts of electricity generation and revenue. 

Destruction of Modules and Materials

Wildfires also can also set PV systems aflame or melt system components, damaging or destroying them.

Destruction of Specialized System Equipment

PV systems have specialized equipment and electronics that maintain their operations and connection to the grid that can also be damaged by wildfires. These can include specialized mechanical motors for PV systems with automated tracking and inverters that convert the direct current produced by the PV modules into alternating current.

These components are costly and may be difficult to replace quickly. For example, an inverter for a 200-kW rooftop PV system could cost $16,000 to replace.

Best Practices

This section outlines the best practices that operators, planners, and purchasers of PV systems may take to reduce the risk and impact of wildfires upon their systems in terms of module and system design, procurement, and site operations and maintenance (O&M).

System Design and Procurement

Research is currently ongoing to identify and improve the production, design, and site design for PV systems to make them more resilient to wildfires. 

Although it is extremely challenging to design PV technology to protect against the exceptional and extreme wildfire events that are becoming more common with climate change, there are methods that PV system operators can use to reduce risk and mitigate damage resulting from a wildfire.

Module Selection

While some types of PV modules may resist fire better than others, all are susceptible to damage from wildfires. The siting selection and environmental management practices of the PV system's owners likely have a greater overall effect on reducing the risk of wildfire damage to a PV system than the specific kind of module. 

The solar industry and its fire regulators have adopted classifications for different grades of PV modules based on their resistance to and resilience against fire events. The National Electric Code and International Building Code have created three designations of PV modules that refer to their ability to withstand fire. They include:

  • Class A – for severe fire exposure; required in wildland-urban interface areas; must withstand direct burning for 10 minutes at a temperature of approximately 1,400 °F and keep flames from spreading more than six feet.
     
  • Class B – for moderate fire exposure; typically required in built-up urban areas; must withstand burning for 10 minutes and keep flames from spreading more than eight feet.
     
  • Class C – for light fire exposure; must withstand burning for four minutes and keep flames from spreading more than 13 feet.

In areas where Class A and B fire ratings are not required for PV systems, owners can take initiative to select these more resilient kinds of PV systems over Class C rated modules to ensure greater resilience to wildfires. 

Keep in mind that even a Class A module is only rated to withstand average fire conditions for 10 minutes, so damage is certainly still possible, but that selection may reduce damage and fire spread when compared to Class C modules and may allow emergency response crews more time to respond. 

Recommendation: Use Class A fire rated modules on sites at high risk for wildfires. In any case, fire ratings of PV modules must at least match the fire rating of the roof. Require fire classifications in accordance with UL 1703, Table 1505.1.

The PV module backsheet material could also help mitigate the damage of wildfires to PV systems. Researchers have experimented with backsheet thickness (ranging from thicknesses of 250-370 micrometers) and material type. Thicker backsheets typically have better fire resistance. Backsheets are typically made up of layers of materials such as fluoroethylene vinyl ether (FEVE), polyvinylidene fluoride (PVDF), polyethylene-vinyl acetate (PET), and polyvinyl fluoride (PVF). An experimental study on the Flammability of Photovoltaic Module Backsheets identified a PVF/PET/PVF three-layer backsheet as the top performer in fire tests, while a two-layer backsheet containing FEVE/PET was the most susceptible to burning.

Recommendation: Choosing a module with a thicker backsheet (300 micrometers or thicker). A three-layer PVF/PET/PVF backsheet may provide more fire resistance than other backsheet compositions.

The coloring of the semiconductor material in a PV module may increase the risk of fire in heavily vegetated areas with arid or semi-arid climates. Darker colored PV modules may be more susceptible to absorbing heat, which could raise the ambient temperature of the surrounding area. During exceptional and concurrent extreme heat and drought events, this can increase the risk of wildfire.

In general, during the module selection process, PV system planners may wish to opt for lighter-colored PV modules for systems in hot climates since the absorption of heat will lead to deficiencies in power generation, regardless of any potential impacts on wildfire occurrence. 

System Considerations

The design of the PV system as a whole, rather than just the PV module alone, can also play a role in improving survivability of a PV system in an area prone to wildfires. Methods, such as vegetation management, protecting sensitive electronic equipment, fire suppression systems, and ease-of-access for firefighters can all reduce the risk of damage or destruction to a PV system during a wildfire.

Defensible space refers to the land area around a critical facility, like a PV system, that site owners manage in ways that reduce the possibility of a wildfire occurring there.

One of the most common ways of creating defensible space is reducing the amount of vegetation that could serve as fuel for a wildfire. The Federal Emergency Management Agency (FEMA) proposes that utilities create defensible space by paving the ground surrounding utility equipment with concrete to prevent the growth of any fuel that could increase fire risk. 

This solution may work for a small-scale PV site where the costs of installing a concrete surface would be more affordable. This solution, however, could create other risks, such as an increase in flooding and runoff risk as well as increasing the heat in summertime operations, which could reduce the PV system's efficiency. Encasing the ground in concrete for large, utility scale sites is likely unfeasible.

Recommendation: Follow FEMA or local fire code guidelines for maintaining a defensible perimeter. If vegetation growth is expected within this defensible perimeter, implement a regular O&M vegetation management plan.

FEMA recommends that utilities place any sensitive infrastructure underground to reduce its risk of wildfire. Although this is not feasible for PV modules themselves, which need to have surface exposure to work effectively, PV owners may underground certain components of a PV system that are not the PV module itself, such as wire and conduits.

Undergrounding these components can be cost prohibitive, make their ongoing maintenance needs more complicated, and may increase the risk of other hazards, such as exposure to flooding. As a lower-cost alternative to a comprehensive undergrounding effort, PV owners may place sensitive wiring, cables, inverters, or energy storage systems inside of fire-resistant containers.

Recommendation: Place electrical equipment such as inverters and batteries inside fire-resistant containers. Underground wire and conduit where practical.

If vegetation management techniques are insufficient to reduce risk or the risk of wildfire is otherwise irreversibly high, the installation of an emergency fire suppression sprinkler system across the PV system might help deter the spread of fire from a wildfire on the outside of the PV site. By default, PV modules are waterproof and can survive exposure to water.
 
It is also important that firefighters can quickly access any part of the PV system that may be on fire or at risk of catching fire. By maintaining a minimum spacing distance between rows for ground-mounted PV systems, fire crews can more easily access fires that are burning in certain sections of the PV system. 

Article 691.10 of the National Electrical Code specifies that PV systems without circuit interrupters must have a fire mitigation plan submitted with the local firefighting authorities, which must identify firefighting access within PV systems. Thus, PV system operators may decide on minimum spacing distances on a case-by-case basis in consultation with their local approving fire safety officials.

Requirement: Follow local fire codes and consult with local fire department on setbacks and spacing to allow access. For sites with battery storage systems, engage local fire crews in fire suppression for the specific battery chemistry.

The addition of a screen in front of or behind a PV system has demonstrated some degree of protection in establishing a minimum setback distance between any flames and the PV system. Installing a physical non-combustible barrier at the rear side of the PV module also has shown some success but may not be feasible for bifacial PV systems as the board blocks light from reaching cells on the underside of the PV module.

Recommendation: Non-combustible screens or barriers can help prevent flames from spreading through a PV system, especially when installed at the rear side of modules.

For roof-mounted PV, the spacing or distance between the underside of the PV module and the surface of the roof can influence the spread and behavior of flames that are burning adjacent to or directly burning the structure upon which the PV system is mounted.

Research by the Underwriters Laboratories has shown that Class A-rated PV systems mounted on Class A-rated, steep-angled rooves with a gap of approximately one foot are better able to resist the spread of flames in the space between the PV system and the roof relative to shallow-angled roofs.

Other research by the University of Edinburgh confirms this finding that an increase in gap height between roof-mounted PV modules and the top of the roof helps reduce the risk of the spread of flames.

Apart from the gap height, a steeper roof angle can generally reduce the risk of fire spread underneath a roof-mounted PV system. The addition of flashing to block the opening to this gap has also demonstrated partial success.

Recommendation: If practical, install modules one foot above roof surface on sites at high risk for wildfire.

Operations and Maintenance

The operators of PV systems should take preemptive actions in their management of their PV systems to avoid the physical and financial impacts of a wildfire event.

Reviewing their warranties and ensuring that fire risk plans are in place can help operators of PV systems avoid the high costs of a business-as-usual approach to operations. 

In terms of physical measures, the removal of potential fuel for fires and the installation of power safety equipment can reduce the risk of wildfire and improve safety for first responders. If a fire has already occurred, techniques to assess the damage and clean surviving panels will help operators of the affected PV systems restore operations.

Recommendation: Implement a regular O&M vegetation management plan.

 

Pre-Damage Techniques or Practices

Before a wildfire happens, operators of PV systems should ensure that any potential sources of fire ignition, like plant materials, are managed around the PV systems to create defensible space around the system. Installing an emergency power-down device for electrical circuits can help firefighters stay safe as they respond to a fire at a PV system so they can focus on neutralizing the fire source.

Post-Damage Techniques or Practices

Post-damage techniques are currently limited as PV systems are generally destroyed if they are burned by a wildfire. Only a rebuild of the damaged sections of the PV system would likely restore the pre-wildfire operating conditions.

If the wildfire avoids burning the PV structures directly, it is still possible that the PV system received some degree of damage through the high air temperatures caused by the fires. Assessments of the potentially affected PV systems will show if any PV modules suffered damage.