CX-036248: Resizing Condensate Lines on 234-4H AHU Steam Preheat Coils

The steam preheating coils for the 234-4H air handling unit (HVAC-AHU-53.006) have been damaged due to water hammer leading to the replacement of t…

Office of NEPA Policy and Compliance

July 20, 2026
Estimated Read Time   min

The steam preheating coils for the 234-4H air handling unit (HVAC-AHU-53.006) have been damaged due to water hammer leading to the replacement of them. In order to rid the system of water hammer, the condensate lines will be resized to 2-1/2" to match the coil's outer size. Per design guidelines for steam systems, condensate lines should not be reduced after the coil until after a steam trap